EPC Modular Online UPS is a highly reliable and adaptable product for medium and large data centers. The series is the upgrade of 20 - 200 kVA series UPS, and the capacity can be expanded to 900 kVA. It provides 150kVA, 180kVA, 250kVA, 300kVA, 500kVA, 600kVA for choosing. Modular IGBT design and isolated air channel ensured its high impact resistance and wide adaptability to harsh environments.
Model | EPC600/30X | EPC500/25X | EPC300/30X | EPC250/25X | EPC180/30X | EPC150/25X |
Grid System | 3 Phases + Neutral + Ground | |||||
Input Voltage Range | 304~478Vac (Line-Line), full load; | |||||
228V~304Vac (Line-Line), load decreases linearly according to the min phase voltage | ||||||
Input Frequency Range | 40Hz~70Hz | |||||
Rated Bypass Voltage | 380/400/415VAC (Line-Line) | |||||
Rated Frequency | 50/60Hz | |||||
Bypass Overload | 110% Long term operation; 110%~125% for 5min; | |||||
125%~150% for 1min; | ||||||
Rated Inverter Voltage | 380/400/415VAC (Line-Line) | |||||
Rated Frequency | 50/60Hz | |||||
Output Power Factor | 1 | |||||
Output Voltage THDu | <1% ( linear load); | |||||
<6% (non-linear load )according to IEC/EN62040-3 | ||||||
Inverter Overload | 110%, 60min; | |||||
125%,10min; | ||||||
150%,1min; | ||||||
>150%,200ms | ||||||
Efficiency | Normal Operation>95%;Battery Operation>95%;ECO Opetation>99% | |||||
Battery Rate Voltage | ±240VDC | |||||
Charger Power | max=20% | |||||
Operation Temperature | 0 ~ 40 ℃ | |||||
Relative Humidity | 0 ~ 95% (Non condensing) | |||||
Noise (1 meter) | 72dB @ 100% load, 68dB @ 45% load | 65dB @ 100% load, 62dB @ 45% load | ||||
Power Module Dimension(W*D*H,mm) | 460*790*134 | |||||
power Module Weight (kg) | 32.3 | |||||
Cabinet Dimension(W*D*H,mm) | 2000*1050*2000 | 600*1100*2000 | 600*1100*1600 | |||
Cabinet Weight (kg) | 660 | 220 | 165 |
● Independent LCD for Each Power Module
Each power module has an independent LCD, gives users’ direct overview of status data and alarms in real time.
● Friendly Interface
Provide graphical and text based information of alarms, status data, instructions that users can have more friendly and safer operation.
● Isolated Air Flow
The dedicated and redundant hot-swappable power modules take the most unique structure design. In this design, the PCB boards and heat sinkers are in two completely different layers, which allows the UPS to run in dusty environments, significantly improving its stability and environmental adaptability.
Cooling air flows in the lower layer, keeping the upper PCB free of dust
One airflow channel ensures fans redundancy, even if one fan fails, the power module can run normally
● Unique Design for High Reliability
Instead of discrete IGBT and SCR components, RM series UPS uses modular IGBT and SCR in Rectifier and Inverter, bringing in extremely high reliability.
All components in one module, less fault points, higher reliability
All components integrated as one modular design, smaller disparity
Less space needed, UPS with compact design and higher power design
Integrated inner thermal sensors display IGBT inner temperature directly
● High Density, Modular, Scalable
High power density, footprint for 300kVA is 0.66m², power density 409kW/m², saving valuable data center space
Scalable from 30kVA to 900kVA, max 30 power modules in parallel
Inherently N+X redundant
Hot swappable power module and bypass & monitoring module
Additional charging module, extra charging current 50A×N for long time back up application
● Comprehensive Monitoring Management
In each power module, information of critical components is monitored and displayed in real time, giving customers a view of inner status of the system and providing reminder information for maintenance.
Maintenance reminder, running time of capacitors and fans displayed and recorded
Comprehensive temperature monitoring for thermal abnormal detection
Intelligent battery charger for long battery life
● Critical Waveform Recording
UPS can record and save the data of the main parameters automatically when faults happen for further analysis.
Can record data information and present as waveform for further analysis
Can easily spot the causes of the failures, avoid future similar faults
● Smart Sleep
Smart Sleep function can intelligently make some power modules go to sleep when load is relatively low, improving the efficiency of the remaining power modules and saving customers on power and cooling costs.
Improving efficiency, reducing power and cooling costs Easy setting with just two steps. Customers can select sleep mode and rotation period
Power modules working in rotation, prolong the life time
● Self-aging
Self-aging is an advanced function applied in all three phase UPS, self-aging function can test UPS under different load situation without real load, saving more than 90% of energy.
Simulate different load conditions without connecting to any real load, saving 90% of energy On site setting supported, easy for factory testing
● Programmable Dry Contacts
Programmable dry contacts are available in all RM and HT33 series UPS. Customers can easily expand or modify the definition of each port.
Abundant options with three inputs and four outputs, all programmable
Easy setting, just pull the drop-down menu and set
Compatible with all the RM and HT33
10 KAKI BUKIT ROAD 1,
#01-16 KB INDUSTRIAL BUILDING,
SINGAPORE - 416175
2024 Eng Hoe Pte Ltd, Singapore. All rights reserved | Disclaimer
Our site uses cookies to provide you with a better experience. By continuing to browse the site you are agreeing to our use of cookies in accordance with our Cookie Policy.