The EPC-VCA series room precision air conditioners are small room-level precision AC that provides temperature, humidity, and cleanliness control for the installation site. The air-conditioning unit adopts a split floor-standing structure, consisting of an indoor unit and an outdoor unit. Air supply mode: Top front supply, downflow supply or upflow supply method. It's used to ensure a reasonable temperature and humidity operating environment for cabinet equipment, server equipment, industrial process equipment, communication equipment, UPS, power distribution equipment, etc.
Unit | EPC-VCA005/VCP007-O | EPC-VCA007/VCP010-O | EPC-VCA012/VCP018-O | EPC-VCA017/VCP024-O | EPC-VCA020/VCP028-O | ||||||
Type | - | KF | Constant | KF | Constant | KF | Constant | KF | Constant | KF | Constant |
Temp&Hum | Temp&Hum | Temp&Hum | Temp&Hum | Temp&Hum | |||||||
cooling | kW | 5.5 | 5.5 | 7.5 | 7.5 | 12.5 | 12.5 | 17 | 17 | 20.5 | 20.5 |
capacity | |||||||||||
SHR | kW | 0.91 | 0.91 | 0.9 | 0.9 | 0.9 | 0.9 | 0.93 | 0.93 | 0.92 | 0.92 |
Air volume | m³/h | 2000 | 2300 | 3200 | 5000 | 5500 | |||||
Heating | kW | - | 3 | - | 3 | - | 3 | - | 6 | - | 6 |
capacity | |||||||||||
Humidification | kg/h | - | 3 | - | 3 | - | 3 | - | 3.0 | - | 3.0 |
capacity | |||||||||||
Compressor | - | Fixed-frequency | |||||||||
Power supply | V | 220V~50Hz 1PH | 380V~50Hz 3PH | ||||||||
Full load | A | 10.5 | 23 | 14.9 | 25 | 10.8 | 21.9 | 14.3 | 25.6 | 14.6 | 26.1 |
current | |||||||||||
Gas pipe size | mm | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 12.7 | 12.7 | 12.7 | 12.7 |
Liquid pipe | mm | 12.7 | 12.7 | 12.7 | 12.7 | 12.7 | 12.7 | 19.05 | 19.05 | 19.05 | 19.05 |
size | |||||||||||
Weight | kg | 62 | 65 | 100 | 120 | 130 |
1. Energy efficient
1> Large air volume, small enthalpy difference, high sensible heat ratio design, to meet the temperature control needs of the server room.
2> High energy-efficient compressor with electronic expansion valve as standard for fast response and more accurate flow adjustment.
3> High efficiency backward tilting centrifugal fan with low energy consumption and high air volume to ensure uniform temperature and humidity distribution in the server room.
4> The use of high-efficiency internally threaded copper tubes and hydrophilic layer-plated open-window aluminum fin evaporators for higher heat transfer efficiency.
5> Outdoor fan with infinitely adjustable speed control, matching condensing pressure operation, energy saving, and noise reduction.
6> Standard with electrode humidifier, higher humidification efficiency, and wider application range.
2. Safe and reliable
1> Use of rigorously certified, high-quality devices to enhance reliability.
2> Products are subjected to rigorous and repeated testing and verification, with high standards required for high-quality delivery.
3> 365 x 24 hours non-stop operation, long-life design, and low maintenance costs.
4> Ultra-wide grid adaptability to avoid frequent start/stop of air conditioners.
5> Highly efficient and environmentally friendly refrigerant R410A as standard.
6>Threaded quick coupling design for no welding on site.
3. Intelligent control
1> 4.3-inch true color touch screen, multi-level password authority, system self- test diagnostic function, more intelligent;
2> Comprehensive monitoring and display of power supply voltage, frequency, phase sequence, cooling capacity, air volume, temperature, humidity curve, and other key information, real-time control of the normal state of the system;
3> Up to 64 air conditioners can be rotated by patrol group control to achieve scheduled rotation, fault rotation, cascading, demand synchronization, anti-competitive operation, etc;
4> Support power-on self-start and timer on/off functions, easy to manage air conditioners;
5> Local storage of not less than 1000 history records, easy to view and trace;
6> Standard RS485 interface, support optional SNMP interface.
4. Customizable
1> Standard with electrode humidifier, support optional wet film humidifier;
2> 100% full frontal maintenance and more flexible installation;
3> Support optional upper pipe / upper drainage to meet the needs of different scenarios;
4> Support AC/EC fans optional according to actual needs;
5> Optional dual power input;
6> A variety of air supply methods to meet a variety of applications;
7> Optional phase tolerance function to better protect the power of air conditioners.